My valve shows the “red hourglass” icon (communication timeout). What should I do?
The red hourglass icon indicates a communication timeout: the valve has not received messages from the Snugr gateway for too long.
How does communication work?
Valves communicate with the Snugr gateway at regular intervals to:
-
receive the temperature setpoint,
-
send the measured temperature (except when a temperature sensor is installed in the same room).
Normal communication intervals:
-
EasyPelt (batteryless / rechargeable): every 10 minutes
-
Battery-powered valves without display: every 10 minutes
-
Battery-powered valves with display: every 5 minutes
A communication error occurs when a valve does not receive any message for more than 1 hour.
Troubleshooting steps
1) Check radio signal quality
In the Snugr interface, check the valve signal level (ideally at least 1 bar out of 4).
Important: the displayed signal level is the signal measured during the last successful communication.
If a timeout is shown, it may not reflect the current signal.
If the signal is weak or missing
-
If the Snugr gateway was moved, try reorienting it or repositioning it.
-
Make sure the antenna on the gateway (and/or repeaters) is:
-
positioned vertically,
-
properly secured: the gold nut at the base should be tightened by hand (do not overtighten) so the antenna stays upright.
-
Optimize the location of the gateway and/or repeaters
If you move the gateway or a repeater, choose an “ideal” location similar to Wi-Fi devices:
-
as close as possible to the devices,
-
with as few direct obstacles as possible (load-bearing walls, metal structures, technical cabinets),
-
avoid placing it inside a closed cabinet, behind a boiler, or in a heavily obstructed technical room.
If the issue persists, a signal repeater or access point may be required. Contact your reseller for more information.
2) If you use a signal repeater
If the valve communicates through a repeater:
-
check that the repeater is still present,
-
properly powered,
-
and located in the same place as when it was installed.
If needed, try a better location using the recommendations above (open area, fewer obstacles).
3) Check the valve power source (depending on the model)
Battery-powered valves
If your valve uses batteries and the steps above are not enough:
-
replace the batteries with 2 × AA 1.5 V non-rechargeable,
-
then check whether communication is restored.
Batteryless (rechargeable) valves
If your valve is an EasyPelt batteryless (rechargeable) model:
-
recharge the valve (preferably using a wall charger),
-
allow enough charging time, then check whether communication resumes at the next communication cycle.
4) Force communication using a calibration (recommended)
To restore communication faster, start a valve calibration procedure.
Reference: How do I start the valve calibration procedure?
Then go to Settings → Devices and check whether the last communication time updates during/after the procedure.